Taieri Collage Boiler Operation Manual
Controls
Main Control Cabnet
Control Cabnet
Icon 1. Control Switch
Auto
Off
Manual
Kindle
Icon 2. Heating
On
Off
Icon 3. Mode Switch
Mode A: School
Mode B: School/Pool
Mode C: Pool
Mode D: Pool Off
Icon 4. Primary Pump Run Lamp
Icon 5. Primary Pump Fault Lamp
Icon 6. Pool Pump Run Lamp
Icon 7. Pool Pump Fault Lamp
Icon 8. Panelview
Icon 9. Pool Heating Lamp
Icon 10. Boiler Run Lamp
Icon 11. Frost Protection Lamp
Icon 12. Inter Block Heat Lamp
Icon 13. Block A Heat Lamp
Icon 14. Block B Heat Lamp
Icon 15. Block C Heat Lamp
Icon 16. Block D Heat Lamp
Icon 17. Hyslop Hall Heat Lamp
Icon 18. Senior Studies Heat Lamp
Icon 19. Music Block Heat Lamp
Icon 20. AV Theatre Heat Lamp
Icon 21. tech block heat lamp
Icon 22. Inter Block Select Button/Lamp
Icon 23. Block A Select Button/Lamp
Icon 24. Block B Select Button/Lamp
Icon 25. Block C Select Button/Lamp
Icon 26. Block D Select Button/Lamp
Icon 27. Hyslop Hall Select Button/Lamp
Icon 28. Senior Studies Select Button/Lamp
Icon 29. Music Block Select Button/Lamp
Icon 30. AV Theatre Select Button/Lamp
Icon 31. Tech Block Select Button/Lamp
Icon 1. Control Switch
Auto: In this position the boilers will run autonomously.
Off: In this position the boilers will not run, but are not to be considered isolated electrically.
Manual: This position is now redundant. If selected the boilers will run uncontrolled
Kindle: This position is now redundant. If selected the boilers will run uncontrolled
Icon 2. Heating
This switch is now redundant in relation to controlling the plc.
Icon 3. Mode Switch
Mode A: School: In school mode the boilers will heat the school only, as and when required by the settings in the panelview.
Mode B: School/Pool: This setting will cause the boilers to heat both the school and the pool simultaniously.
Mode C: Pool: Heats the pool only.
Mode D: Pool Off: This signifies that the pool is not to be used as a heat sink. I believe this would be better described as "school not pool".
Icon 4. Primary Pump Run Lamp
This lamp will be illuminated when the primary circulating pump is running.
Icon 5. Primary Pump Fault Lamp
This lamp will be illuminated if the primary pump becomes overloaded.
Icon 6. Pool Pump Run Lamp
This lamp will be illuminated when the pool circulating pump is running.
Icon 7. Pool Pump Fault Lamp
This lamp will be illuminated if the pool pump becomes overloaded.
Icon 8. Panelview
The primary means of controlling the settings for the plc.
Icon 9. Pool Heat Lamp
This lamp will be illuminated when the pool is calling for heat.
Icon 10. Boiler Run Lamp
This lamp will be illuminated when the boilers are running.
Icon 11. Frost Protection Lamp
This lamp will be illuminated if the temperature outside falls below the frost protection thermostat setpoint. If this happens, all valves will open and both circulating pumps will run continuously. The boilers will not be asked to run, but will not be stopped from doing so if they would normally have been running.
Icon 12. Inter Block Heat Lamp
This lamp will be illuminated if the Inter Block is calling for heat.
Icon 13. Block A Heat Lamp
This lamp will be illuminated if Block A is calling for heat.
Icon 14. Block B Heat Lamp
This lamp will be illuminated if Block B is calling for heat.
Icon 15. Block C Heat Lamp
This lamp will be illuminated if Block C is calling for heat.
Icon 16. Block D Heat Lamp
This lamp will be illuminated if Block D is calling for heat.
Icon 17. Hyslop Hall Heat Lamp
This lamp will be illuminated if Hyslop Hall is calling for heat.
Icon 18. Senior Studies Heat Lamp
This lamp will be illuminated if Senior Studies is calling for heat.
Icon 19. Music Block Heat Lamp
This lamp will be illuminated if the Music Block is calling for heat.
Icon 20. AV Theatre Heat Lamp
This lamp will be illuminated if the AV Theatre is calling for heat.
Icon 21. Tech Block Heat Lamp
This lamp will be illuminated if the Tech Block is calling for heat.
Icon 22. Inter Block Select Button/Lamp
This button is used for selecting the zone when the panelview has put the plc into instant heat mode. When the zone is selected the button will become illuminated.
Icon 23. Block A Select Button/Lamp
This button is used for selecting the zone when the panelview has put the plc into instant heat mode. When the zone is selected the button will become illuminated.
Icon 24. Block B Select Button/Lamp
This button is used for selecting the zone when the panelview has put the plc into instant heat mode. When the zone is selected the button will become illuminated.
Icon 25. Block C Select Button/Lamp
This button is used for selecting the zone when the panelview has put the plc into instant heat mode. When the zone is selected the button will become illuminated.
Icon 26. Block D Select Button/Lamp
This button is used for selecting the zone when the panelview has put the plc into instant heat mode. When the zone is selected the button will become illuminated.
Icon 27. Hyslop Hall Select Button/Lamp
This button is used for selecting the zone when the panelview has put the plc into instant heat mode. When the zone is selected the button will become illuminated.
Icon 28. Senior Studies Select Button/Lamp
This button is used for selecting the zone when the panelview has put the plc into instant heat mode. When the zone is selected the button will become illuminated.
Icon 29. Music Block Select Button/Lamp
This button is used for selecting the zone when the panelview has put the plc into instant heat mode. When the zone is selected the button will become illuminated.
Icon 30. AV Theatre Select Button/Lamp
This button is used for selecting the zone when the panelview has put the plc into instant heat mode. When the zone is selected the button will become illuminated.
Icon 31. Tech Block Select Button/Lamp
This button is used for selecting the zone when the panelview has put the plc into instant heat mode. When the zone is selected the button will become illuminated.